The short answer: about four 550 W panels refill a 10.24 kWh battery from 20% to full on a day with 5 peak sun hours. That is before the panels also run the home during the day, which usually adds one or two panels.
The formula
Panels = battery kWh × 0.8 ÷ 0.8 ÷ (peak sun hours × panel kW).
- × 0.8: the energy to put back, refilling from about 20% to full.
- ÷ 0.8: about 20% lost between the panels and the battery, through heat, dust, wiring and charging.
- Peak sun hours: the day’s sunshine expressed as hours of full sun (1 kW per m²). Across Nigeria, Kenya, Pakistan and the Philippines the yearly average is roughly 4.5 to 6 hours a day, lower in the rainy season. Global Solar Atlas gives the figure for any site.
Panels to refill each battery size
| Battery | 4 sun hours | 5 sun hours | 6 sun hours |
|---|---|---|---|
| 5 kWh (5.12 kWh) | 3 (1.3 kW) | 2 (1.0 kW) | 2 (0.9 kW) |
| 10 kWh (10.24 kWh) | 5 (2.6 kW) | 4 (2.0 kW) | 4 (1.7 kW) |
| 16 kWh (16.08 kWh) | 8 (4.0 kW) | 6 (3.2 kW) | 5 (2.7 kW) |
| 20 kWh (20.48 kWh) | 10 (5.1 kW) | 8 (4.1 kW) | 7 (3.4 kW) |
550 W panels, refilling 80% of the rated capacity with about 20% system losses. Rounded up to whole panels.
Add the daytime load
During the day the panels also run whatever is switched on. A home using an average of 300 W for 8 daylight hours needs another 2.4 kWh. At 5 peak sun hours that is about 0.6 kW of extra panels: two more 550 W panels, rounded up. Add the daytime load first, then the battery.
Check the inverter before adding panels
- Maximum PV input. The array should not exceed the inverter’s rated PV input: for example 5,500 W on the KNY5000 in our ZC-S stackable system and 2 × 5,500 W on the KNY11000S.
- Voltage window. Panels in series add their open-circuit voltage, which rises on cold mornings. Keep each string inside the inverter’s MPPT and maximum PV voltage.
- Charge current. 100 A into a 51.2 V battery is about 5 kW of charging, the recommended figure for our 10–20 kWh units; for 5 kWh units keep it at or below 50 A.