Guide · 4 min read

How long will a 10 kWh battery power a home?

About 8 hours at 1 kW, and much longer for essentials only. Here is the formula, a runtime table and what changes the answer.

The short answer: a 10.24 kWh battery runs a steady 1 kW load for about 8 hours, a 300 W load for about 27 hours, and a 2 kW load for about 4 hours. Those figures use 80% of the stored energy, before inverter losses. For a home running only essentials (lights, fans, a fridge, TV and Wi-Fi, about 300 to 500 W), that is roughly 16 to 27 hours.

The formula

Hours = rated kWh × 0.8 × inverter efficiency ÷ load in kW. With a 10.24 kWh battery, 80% usable and 90% inverter efficiency, that is 7.4 kWh of AC energy to spend.

Runtime at different loads

Average loadBefore inverter lossesWith 90% inverter efficiency
100 W81.9 h73.7 h
300 W27.3 h24.6 h
500 W16.4 h14.7 h
1,000 W8.2 h7.4 h
1,500 W5.5 h4.9 h
2,000 W4.1 h3.7 h
3,000 W2.7 h2.5 h
5,000 W1.6 h1.5 h

10.24 kWh battery (51.2 V, 200 Ah), 80% usable. Real runtime also depends on temperature and the inverter’s own consumption.

What typical appliances draw

ApplianceTypical power
LED bulb5–10 W each
Wi-Fi router10–15 W
Laptop40–65 W
LED TV, 43 inch60–100 W
Fan40–75 W
Fridge or chest freezer100–200 W while the compressor runs; about 40–60 W on average over a day
Water pump, 0.5–1 HP370–750 W while running
Air conditioner, 1.5 HP1,100–1,400 W; less for inverter types at part load
Microwave1,000–1,200 W
Kettle1,800–2,200 W

An example evening

Ten LED bulbs (80 W), a TV (80 W), two fans (120 W), a fridge averaging 50 W and a Wi-Fi router (10 W) add up to about 340 W. A 10 kWh battery runs that for about 22 hours after inverter losses: a whole night and most of the next day.

Add a 1.5 HP air conditioner at about 1,200 W and the total becomes about 1.5 kW, which brings the runtime down to about 5 hours.

What shortens or extends runtime

  • Heavy loads. Air conditioners, pumps, kettles and irons use most of the energy. Running them while the sun is up saves the battery for the night.
  • Cold. LiFePO4 batteries deliver less energy in the cold. Ours discharge from -20 °C but charge only from 0 °C.
  • Reserve settings. Many inverters keep a reserve, such as 20%, for backup. That energy is not used in daily cycling.
  • Solar. With panels recharging the battery each day, a 10 kWh battery only has to cover the hours without sun.
  • A second battery. Two 10 kWh units in parallel double the runtime and halve the current each one supplies.

Need help sizing a system?

Send us the loads, the inverter and the market. We recommend a battery and reply with the datasheet and price.