Lithium or tubular battery for an inverter?

Both store energy for the same 48 V inverter. What changes is how much of it you can use, how often you can cycle it, how fast it recharges and how much looking after it needs.

The short answer: if the battery is cycled every day, through daily power cuts or as solar storage, a LiFePO4 battery gives more usable energy per rated kWh, far more cycles and faster recharging, in one unit instead of four. A tubular bank costs less to buy and can still suit a home that only needs backup now and then.

Same inverter, two kinds of battery

A 48 V inverter runs on either. A tubular bank is four 12 V lead-acid batteries in series. A lithium battery for the same inverter is one 51.2 V unit, built from sixteen 3.2 V LiFePO4 cells.

Side by side

Tubular lead-acid bankLiFePO4 battery
For a 48 V inverterFour 12 V batteries in seriesOne 51.2 V unit
Example4 × 12 V 200 Ah = 9.6 kWh on paper51.2 V 200 Ah = 10.24 kWh
Energy used day to dayAbout half: about 4.8 kWhAbout 80%: about 8.2 kWh
Cycle lifeDepends heavily on depth of discharge; check the maker’s figure at the depth you will use6,000 cycles at 80% depth of discharge on our KNY 51 series; 8,000 on some 15 and 16 kWh models
RechargingSlows down near full, and needs regular full chargesTakes its recommended current until nearly full: 100 A on our 10–20 kWh units
Looking after itFlooded types need distilled-water top-ups and ventilationSealed; a battery management system protects the cells
MonitoringVoltage onlyState of charge over CAN / RS485; Bluetooth, WiFi or a touch screen on some models
SpaceFour batteries side by sideOne floor-standing or wall-mounted unit; the 10.24 kWh KNY 51200 weighs 101 kg

Why usable energy matters more than the label

Four 12 V 200 Ah tubular batteries make 9.6 kWh on paper. They are usually discharged to only about half, to protect their life, so about 4.8 kWh is used each night. A 51.2 V 200 Ah LiFePO4 battery stores 10.24 kWh and gives about 8.2 kWh at 80%. With a similar label, the lithium battery delivers about 1.7 times the energy per night.

BatteryOn paperUsed each nightHours at 500 W
Tubular, 4 × 12 V 200 Ah9.6 kWh4.8 kWh8.6 h
LiFePO4, 51.2 V 200 Ah10.24 kWh8.2 kWh14.7 h

When tubular still makes sense

  • Power cuts are rare and short, so the battery is seldom cycled.
  • The budget for the battery itself is the deciding factor today.
  • The inverter cannot be set for lithium and will not be replaced.

Switching an existing inverter to lithium

  • Replace the whole 12 V bank with one 51.2 V unit. Do not mix lithium and lead-acid batteries in one bank.
  • Set the battery type to lithium, or connect the CAN / RS485 cable so the inverter reads the battery’s state of charge directly.
  • If you set the values by hand: charge voltage 58 V recommended and never above 58.4 V; low-battery cut-off at the battery’s recommended value, 44–46 V on our 51.2 V models.
  • Set the maximum charge current to the battery’s recommended figure: 100 A on our 10–20 kWh units.

See what size battery a 5 KVA inverter needs for sizing by inverter.