Hybrid solar inverter
XD series
Three 48 V hybrid inverters from 6.6 to 10.6 kW in an IP66 case. Each has two MPPT inputs for up to 18,000 W of solar, switches automatically between grid and a diesel generator, and runs up to 9 units in parallel.
IP66protection rating
6.6–10.6 kWrated output
18,000 Wmax. PV input
9units in parallel
Highlights
Why installers choose XD series
IP66 enclosure
Rated IP66 against dust and water.
Grid and generator
Two independent AC inputs (mains and generator) with automatic switching.
Programmable priority
Set the supply priority between solar, battery and grid.
Lead-acid or lithium
Works with both; RS485 port for lithium battery BMS communication.
Specifications
XD series technical data
Swipe sideways to see all models →
| Model | XD6648 | XD8648 | XD16048 |
|---|---|---|---|
| General | |||
| Phase | Single-phase input, single-phase output | ||
| Rated output power | 6,600 VA / 6,600 W | 8,600 VA / 8,600 W | 10,600 VA / 10,600 W |
| Max. PV input power | 12,000 W | 16,000 W | 18,000 W |
| Max. charging power | 6,600 W | 8,600 W | 10,600 W |
| Output | |||
| Rated voltage | 220 / 230 / 240 VAC ± 5% | ||
| Output voltage range | 184–264.5 VAC / 195.5–253 VAC / 182–260 VAC ± 3 V | ||
| Rated output current | 28.7 A | 37.4 A | 46.1 A |
| Power factor | > 0.99 | ||
| Peak efficiency (DC/AC) | 95% | 96% | 96% |
| AC input | |||
| AC start voltage / auto-restart voltage | 60–80 VAC / 180 VAC | ||
| Grid voltage range | 90–280 VAC / 170–280 VAC | ||
| Grid frequency range | 50 / 60 Hz ± 0.1% | ||
| Max. grid current | 40 A | 60 A | 60 A |
| PV input | |||
| Max. PV input voltage | 500 VDC | ||
| MPPT operating range | 120–450 VDC | ||
| MPPT inputs / max. current per input | 2 / 21 A | 2 / 27 A | 2 / 27 A |
| Battery-mode output | |||
| Rated output voltage | 220 / 230 / 240 VAC | ||
| Output waveform | Pure sine wave | ||
| Conversion efficiency (DC to AC) | 93% | ||
| Battery | |||
| Battery type | Lead-acid or lithium-ion | ||
| Battery voltage range | 40–60 VDC | ||
| Rated DC voltage | 48 VDC | ||
| Max. PV charging current | 135 A | 190 A | 210 A |
| Max. AC charging current | 135 A | 190 A | 210 A |
| Max. charging current | 135 A | 190 A | 210 A |
| Interface | |||
| Parallel operation | Up to 9 units | ||
| Communication | RS232 / RS485, Wi-Fi | ||
| Environment | |||
| Protection rating | IP66 | ||
| Humidity | 20–90% (non-condensing) | ||
Data from the 2026 inverter catalogue. Specifications may change; we confirm the current datasheet with every quotation.