White off-grid solar inverter with round grey display panel
Off-grid solar inverter

UD Pro+ series

Two 48 V off-grid inverters, 5 kW and 10 kW, with MPPT solar charging. Up to 9 units can work together in parallel, including three-phase setups, and the charging voltage can be set from 48 to 61 V.

5 / 10 kWrated output
48 Vbattery voltage
9units in parallel
120 Amax. solar charging
Highlights

Why installers choose UD Pro+ series

Parallel to 9 units

Expand the system with up to 9 units, three-phase parallel included.

Power-saving mode

High-efficiency design with a power-saving mode.

Auto restart

Restarts automatically when mains power comes back.

Lithium, Wi-Fi, dry contact

Supports lithium battery communication, external Wi-Fi and a dry contact.

Specifications

UD Pro+ series technical data

ModelUD6348AMBUD12548AMB
AC input
AC input voltage220 VAC (standard)
Input voltage range90–275 VAC ± 3 V (normal mode), 170–275 VAC ± 3 V (UPS mode)
Input frequency50 / 60 Hz ± 5%
Output
Rated output power5,000 W10,000 W
Output voltage on mainsSame as the input voltage
Output frequency on mainsSame as the input frequency
Output voltage on battery220 VAC ± 10%
Output frequency on battery50 or 60 Hz ± 1%
Output waveform on batteryPure sine wave
Transfer time≤ 10 ms (UPS mode) / ≤ 20 ms (inverter mode)
Load peak ratio3 : 1 (max.)
Battery
Battery typeLead-acid, gel, flooded or lithium (external)
Battery voltage48 VDC
Battery charging voltage56.4 VDC (settable 48–61 V)
Solar & AC charger
Max. PV array power3,200 W6,400 W
Solar input voltage rangeMPPT 60–150 VDC (200 VDC on request)
Max. PV open-circuit voltage150 VDC (200 VDC on request)
Max. solar charging current120 A
Max. AC charging current50 A100 A
Protection & interface
ProtectionOn mains: input over-current fuse. On battery: overload, short-circuit and low-voltage protection, battery reverse-connection protection (fuse)
Status displayAC voltage and frequency, PV voltage and current, output voltage and frequency, battery voltage, load current and more (page keys)
InterfaceRS232, lithium battery BMS communication, parallel interface, dry contact card
Environment
Operating temperature-10 to 50 °C
Storage temperature-15 to 45 °C
Humidity20–95% (non-condensing)
Noise< 45 dB
Size (L × W × H)527 × 330 × 149 mm545 × 400 × 200 mm

Data from the 2026 inverter catalogue. Specifications may change; we confirm the current datasheet with every quotation.